The S5 collects Real-time data at the System, String and Unit Level Data includes:
- Ambient Temperature
- Delta Temperature
- Float/Discharge Voltage Data.
- Unit (cell or jar)
- Float/Discharge Voltage,
- Float/Discharge Temperature,
- Unit Impedance
Battery Types
NERC Recommended Monitoring Parameters
- High and Low Float Voltage
- Electrolyte Level Monitoring
- DC Ground Fault
- Proper Float Voltage
- String Continuity
- Inter-cell Connections
- Internal Ohmic Values with Baselines
Compliance Eliminates all or most maintenance intervals
Hardware Capabilities
Interfaces
Front: USB (Type B), Serial (DB-9F)
Rear Panel
Integrated Network Card - Ethernet (10BaseT),
(6) NO/NC programmable Dry contact Outputs
(4) NO/NC programmable Dry contact Inputs
Protocols
- SNMP version 1 Communications
- Modbus Over TCP/IP Communications
- DNP3 (External Protocol Converter)